Capacity |
100KVA |
120KVA |
160KVA |
200KVA |
250KVA |
300KVA |
400KVA |
500KVA |
600KVA |
Input |
Voltage range (Vac) |
380/400/415VAC (±25%, can be set through the LCD panel) |
Frequency range (Hz) |
40-70Hz, automatically select the synchronous range according to the grid frequency, and adapt to the 50/60Hz frequency system |
Bypass synchronous tracking range (Hz) |
50±5% (±10% is optional) |
Number of rectification pulses |
12-pulse rectification |
Phase system |
3φ4W+PE (Three-phase five-wire system) |
Battery voltage (VDC) |
384 |
480 |
Number of battery cells |
32 battery cells are standard configuration (The number of battery cells can be set through the LCD panel, ranging from 30 to 33 cells) |
40 battery cells are standard configuration (The number of battery cells can be set through the LCD panel, ranging from 38 to 42 cells) |
Power factor |
0.8 |
Output |
Voltage (V) |
Line-Neutral: 220±1%, Line-Line: 380±1% |
Voltage stability of three-phase 100% load unbalance |
<2%, 100% unbalance is allowed |
Frequency (Hz) |
When the mains power is normal, it tracks the mains frequency; when the mains power is abnormal, it is 50±0.2% |
Transfer Time (ms) |
0 |
Parallel operation mode (parallel model) |
Up to 8 units can be paralleled |
Waveform distortion |
Total Harmonic Distortion (THD) < 3% for linear loads; Total Harmonic Distortion (THD) < 5% for non-linear loads |
Overload capacity |
It can maintain operation for 10 minutes at 125% full load, and for 1 minute at 150% full load and then switch to bypass power supply. After the load returns to normal, it can automatically switch back to inverter operation. |
Peak factor |
3:1 |
Others |
Manual maintenance bypass |
A manual maintenance bypass switch without conversion time is standard configuration. |
Communication function |
It provides dry contact signals and RS232/RS485 communication interfaces. You can optionally configure an SNMP card, WeChat manager, etc. to achieve remote communication and management. |
Panel display |
The LED displays the working status and fault indications; the LCD displays the three – phase input voltage, input frequency, three – phase output voltage, load, battery voltage, battery charging and discharging current, etc. |
Display mode |
It features a 7 – inch color LCD touch – screen display. |
Noise (dB) |
<65 dB (within 1 – meter distance) |
Alarm function |
Alarms for low battery voltage, abnormal mains power, overload, UPS failure, over – temperature protection, etc. |
Protection function |
Protection functions include input over – voltage protection, under – voltage protection, battery under – voltage protection, overload protection, short – circuit protection, over – temperature protection, etc. |
Cooling method |
Forced air cooling |
Operating temperature (°C) |
0~40°C |
Relative humidity |
0~95%, non – condensation |
Dimensions:
D × W × H (mm) |
800×1100×1800 |
1113×1405×2005 |
1113×1605×2005 |
1200×2600×2000 |
Weight (T) |
0.89 |
1.08 |
1.28 |
1.38 |
1.68 |
1.98 |
2.48 |
2.85 |
3.15 |