SAI de torre de doble conversión Rhimo RM33-10-80K-H

The high-frequency Tower UPS RM33-H series 10 – 80kVA fully digitally controlled online double-conversion three-phase input and three-phase output UPS offers several advantages, including high overall efficiency, high input power factor, low input current harmonics, and excellent output quality. It can eliminate various power grid issues and provide customers with stable and reliable power protection.

RANGO DE POTENCIA

10-80kva

FASE DE POTENCIA

Fase 3/3

 

Categoría: Etiqueta:

SOLICITUD

This product has a wide range of applications, offering safe,stable, reliable, and environmental  friendly power support
for critical loads in various industries such as telecommunications, finance, education, transportation, radio and television, medical care, and manufacturing.

Características

high reliability

  • Ultra – wide input voltage range, adapting to harsh power grid environments.
  • Wide input frequency range, allowing the connection of fuel-powered generators.
  • Supports direct startup from the battery in the absence of mains power.
  • Equipped with an EPO (Emergency Power Off) interface.

high-efficiency and green

  • The overall machine efficiency is greater than or equal to 95.5%.
  • The input power factor is as high as 0.99, and the input harmonic current is less than 3%.

High practicality

  • It has an extremely strong load-carrying capacity, strong load adaptability, and is compatible with generator operation.
  • It supports the parallel connection of 4 units and the sharing of battery packs.
  • It supports no-load aging tests.

Good usability

  • It is equipped with a 4.3-inch color touch screen, making it easy to operate.
  • It has intelligent management functions and supports RS485, SNMP, dry contacts, and CAN interfaces.
model : RM33- 10K-H 20K-H 30K-H 40K-H 60K-H 80K-H
capacidad 10 kVA 20 kVA 30 kVA 40 kVA 60KVA 80KVA
Aporte Input Wiring Three-phase Five-wire
Rated Input Voltage 380/400/415Vac
Input Voltage Range 138~485Vac
Input Frequency Range 40HZ-70Hz
Input Power Factor ≥0,99
Input Current Harmonic (THDi) <3% (100% linear load)
Bypass Voltage Range For 220Vac: The upper limit is 25% (optional +10%, +15%, +20%);For 230Vac: The upper limit is 20% (optional +10%, +15%);For 240Vac: The upper limit is 15% (optional +10%);The lower limit is -45% (optional -10%, -20%, 30%).
Generator Connection support
cableado de salida Three-phase five-wire system
producción Rated output voltage 380/400/415Vac
Factor de potencia de salida 0.9
voltage regulation ±1%
Frecuencia Mains mode: ±1%/ +2%/ +4%/ +5%/ +10% adjustable; Battery mode: (50/60 ± 0.1%)Hz
Peak current ratio 3:1
Output voltage harmonic (THDV) <2% (100% linear load); <4% (100% non-linear load)
Overall efficiency 95.5%
Capacidad de sobrecarga At 110% load, switch to bypass after 60 minutes; at 125% load, switch to bypass after 10 minutes; at 150% load, switch to bypass after 1 minute
batería Voltaje de la batería ±180V/192V/±204V/±216V/±228V/±240V/±252V/+264V/+276V/+288V/+300Vdc (30-50 sections optional)
Charge Current Maximum 10A Maximum 15A Maximum 20A
Tiempo de transferencia Cambio del modo de red al modo bypass: 0 ms (seguimiento); Cambio del modo de red al modo batería: 0 ms
Environ ment Operating temperature 0°C to 40°C
Temperatura de almacenamiento -25°C to 55°C
Humidity range 0 to 95% (non-condensing)
Operating altitude Less than 1500 meters
Ruido (a una distancia de 1 metro) Less than 55 decibels Less than 58 decibels Less than 60 decibels
function Alarm function Múltiples funciones de alarma por sobrecarga, anomalías de red, fallos del SAI, subtensión de batería, etc.
Protection function Alarms for battery under – voltage, output over- and under – voltage, short – circuit, overload, over – temperature, fan failure, lightning protection
Communication interface CAN, RS485, FE, LBS, tarjeta de operación paralela, adaptador SNMP (opcional), tarjeta de relé (opcional)
other W × D × H (mm) 710x250x535 780x280x600 880 × 280 × 880 885x440x1200
Net Weight (kg) 30 36.4 39.4 14 68.2 150
Execution standards YD/T 1095-2018