랙마운트 모듈형 UPS RM UM 시리즈 10-200kva

The RM-UM series Rackmount modular UPS can be installed and used independently as a tower model, and it is also suitable for standard 19-inch network cabinets. By adopting the online double-conversion technology, it can completely eliminate various power grid problems and provide customers with stable, pure sine power protection.

 

카테고리:

애플리케이션
This product has a wide range of applications, providing safe, stable, reliable, and environmentally friendly power support for critical loads in various industries such as telecommunications, finance, education, transportation, radio and television, medical care, and manufacturing.

 

FEATURES

높은 신뢰성

  • Ultra-wide input voltage range, which enables it to adapt to harsh power grid environments.
  • Large input frequency range, allowing connection to fuel generators.

High Efficiency and Green

  • The overall efficiency of the unit is greater than or equal to 95%.
  • 입력 역률은 0.99로 높고, 입력 고조파 전류는 3%보다 낮습니다.

Strong Practicality

  • It has an extremely strong load-bearing capacity and excellent load adaptability.
  • It is suitable for standard network cabinets and integrated power distribution cabinets to form a backup power supply system.

Good Usability

  • Equipped with a 4.3/7-inch color touch screen, making it easy to operate and maintain.
  • It has intelligent management functions and supports RS485, SNMP, dry contact, and CAN interfaces.

SPECIFICATIONS OF 12-PULSE MODEL

Model :RM33- 100K-P12 120K-P12 160K-P12 200K-P12 250K-P12 300K-P12 400K-P12 500K-P12 600K-P12
용량 100KVA 120KVA 160KVA 200KVA 250KVA 300KVA 400KVA 500KVA 600KVA
입력 전압 범위(Vac) 380/400/415VAC (±25%, can be set through the LCD panel)
주파수 범위(Hz) 40-70Hz, automatically select the synchronous range according to the grid frequency, and adapt to the 50/60Hz frequency system
Bypass synchronous tracking range (Hz) 50±5% (±10% is optional)
Number of rectification pulses 12-pulse rectification
Phase system 3φ4W+PE (Three-phase five-wire system)
Battery voltage (VDC) 384 480
Number of battery cells 32 battery cells are standard configuration (The number of battery cells can be set through the LCD panel, ranging from 30 to 33 cells) 40 battery cells are standard configuration (The number of battery cells can be set through the LCD panel, ranging from 38 to 42 cells)
역률 0.8
산출 Voltage (V) Line-Neutral: 220±1%, Line-Line: 380±1%
Voltage stability of three-phase 100% load unbalance <2%, 100% unbalance is allowed
Frequency (Hz) When the mains power is normal, it tracks the mains frequency; when the mains power is abnormal, it is 50±0.2%
Transfer Time (ms) 0
Parallel operation mode (parallel model) Up to 8 units can be paralleled
Waveform distortion Total Harmonic Distortion (THD) < 3% for linear loads; Total Harmonic Distortion (THD) < 5% for non-linear loads
과부하 용량 It can maintain operation for 10 minutes at 125% full load, and for 1 minute at 150% full load and then switch to bypass power supply. After the load returns to normal, it can automatically switch back to inverter operation.
Peak factor 3:1
Others Manual maintenance bypass A manual maintenance bypass switch without conversion time is standard configuration.
Communication function It provides dry contact signals and RS232/RS485 communication interfaces. You can optionally configure an SNMP card, WeChat manager, etc. to achieve remote communication and management.
Panel display The LED displays the working status and fault indications; the LCD displays the three – phase input voltage, input frequency, three – phase output voltage, load, battery voltage, battery charging and discharging current, etc.
Display mode It features a 7 – inch color LCD touch – screen display.
Noise (dB) <65 dB (within 1 – meter distance)
알람 기능 Alarms for low battery voltage, abnormal mains power, overload, UPS failure, over – temperature protection, etc.
보호 기능 Protection functions include input over – voltage protection, under – voltage protection, battery under – voltage protection, overload protection, short – circuit protection, over – temperature protection, etc.
Cooling method Forced air cooling
Operating temperature (°C) 0~40°C
Relative humidity 0~95%, non – condensation
Dimensions:
D × W × H (mm)
800×1100×1800 1113×1405×2005 1113×1605×2005 1200×2600×2000
Weight (T) 0.89 1.08 1.28 1.38 1.68 1.98 2.48 2.85 3.15

MAIN PERFORMANCE PARAMETERS

용량 10-200KVA
입력 입력 배선 Three phase five wire
Rated input voltage 380/400/415Vac
Input Voltage 138~485Vac
Input frequency range 40Hz-70Hz
Input power factor ≥ 0.99
Input current harmonics (THDI) ≤ 3% (100% linear load)
Bypass voltage range 220Vac upper limit: 25% (optional+10%, +15%,+20%) 230Vac upper limit: 20% (optional+10%,+15%)
240Vac upper limit: 15% (optional+10%) Lower limit: -45% (optional -10%, -20%, -30%)
Frequency protection range ± 10%
Generator connection 지원하다
산출 출력 배선 Three phase five wire
rated output voltage 380/400/415Vac
출력 역률 0.9 or 1
전압 정확도 ±1%
출력 주파수 상업용 전원 모드 ± 1%, ± 2%, ± 4%, ± 5%, ± 10% can be set
배터리 모드 (50/60±0.1%)Hz
피크 전류 비율 3:1
Output voltage harmonics (THDV) < 2% (100% linear load); < 4% (100% non-linear load)
과부하 용량 110% load, continue for 60 minutes and then switch to bypass; 125% load, continue for 10 minutes and then switch to bypass; 150% load, continue for 1 minute and then switch to bypass
배터리 battery voltage ± 180V/192V/± 204V/± 216V/± 228V/± 240/± 252/± 264/± 276/± 288/± 300Vdc (30-50 sections optional)
충전 전류(A) 내각 2 slots 20A/4 slots 40A/6 slots 60A 2 slots 30A/4 slots 60A
기준 치수 최대 10A Maximum 15A
환승 시간 메인 모드에서 바이패스 모드로 전환: 0ms(추적); 메인 모드에서 배터리 모드로 전환: 0ms
통신 인터페이스 CAN,RS485,FE,LBS, Parallel card, SNMP adapter (optional), relay card (optional)
Function caution function Multiple alarm functions such as overload, abnormal mains power, UPS failure, battery undervoltage, etc
보호 기능 Battery undervoltage, output undervoltage, short circuit, overload, overheating, fan fault alarm, lightning protection
환경 작동 온도 0°C~40°C
storage temperature -25°C~55°C
습도 범위 0~95% (non condensing)
Working altitude <1500미터

Rack/Tower Compatible Models

Cabinet capacity 20\30kVA 40\60kVA 60\90\120\150kVA
Maximum number of modules 2 4 6 (30kVA module: 5+1 redundancy)
Compatible power module 10\15kVA 10\15kVA 10\15\20\25\30kVA
Cabinet size: D × W × H (mm) 750 × 545 × 649 750 × 545 × 827 750 × 545 × 1005
MODULE SIZE: W × D × H (mm) 440 × 620 × 86mm
Cabinet weight (kg) 63 75 87
Module weight (kg) 10/15/20kVA: 20.8; 25/30kVA: 21.6 10/15/20kVA: 20.8; 25/30kVA: 21.6 10/15/20kVA: 20.8; 25/30kVA: 21.6

Pure Rack Mounted Models

Cabinet capacity 40\50\60\100kVA 80\100\120\200kVA 120\150kVA
Maximum number of modules 2 4 6 (30kVA module: 5+1 redundancy)
Compatible power module 20\25\30\50kVA 20\25\30\50kVA 20\25\30kVA
Cabinet size: D × W × H (mm) 40\50\60kVA: 835 × 485 × 356
100kVA: 485 × 825 × 489.5
80\100\120kVA: 835 × 485 × 534
200kVA: 485 × 835 × 756.5
485 × 835 × 712
MODULE SIZE: W × D × H (mm) 20/25/30kVA: 620 × 440 × 86
50kVA: 440 × 620 × 131
20/25/30kVA: 620 × 440 × 86
50kVA: 440 × 620 × 131
20/25/30kVA: 620 × 440 × 86
Cabinet weight (kg) 40\50\60kVA: 44.5
100kVA: 50
80\100\120kVA: 53.5
200kVA: 72.5
63.5
Module weight (kg) 20kVA: 20.8; 25/30kVA: 21.6; 50kVA: 33 20kVA: 20.8; 25/30kVA: 21.6; 50kVA: 33 20kVA: 20.8; 25/30kVA: 21.6
위로 스크롤