Modular online data center UPS RM FM series 50-600KVA

The high-frequency modular RM33-FM series 50 – 600kVA modular UPS adopts digital control, modular design, and N+X parallel redundancy technology. The product’s capacity covers all power segments from 50kVA to 600kVA, which facilitates users to configure flexibly and make step-by-step investments. Up to 4 units can be paralleled to reach a capacity of 2400kVA.

POWER RANGE

50-600kva

POWER PHASE

3/3 phase

 

Category:

APPLICATION

This product has a wide range of applications and provides safe, stable, reliable, and environmentally friendly power support for critical loads in various industries such as telecommunications, finance, education, transportation, radio and television, medical care, and manufacturing.

Product Features

Advanced Technology

  • Adopting digital control, it boasts excellent performance and can connect completely unbalanced loads.
  • The overall efficiency of the unit is as high as 96%.
  • The output power factor is 1.

High Reliability

  • The centralized control unit features redundant parallel connection. The failure of one part will not affect the operation of the entire unit, and the availability of N+X parallel redundancy reaches 99.999%.
  • The centralized monitoring module has the hot-swappable function. It uses centralized bypass power supply, which improves the power supply capacity of the bypass.
  • It has the EPO (Emergency Power Off) function and also has the remote emergency power off (REPO) function.

Convenience and Flexibility

  • With a modular design, users can flexibly increase the number of modules.
  • The downtime for maintenance is short. When an emergency occurs in the UPS, maintenance personnel can safely perform online repairs.
  • It is equipped with a touch color screen display, providing abundant UPS status information, warning information, fault information, etc.

Intelligent Design

  • The battery capacity and charging current can be set on the LCD screen, realizing the automatic and smooth switching of the charging mode.
  • It adopts an advanced two-stage three-phase intelligent charging method, taking into account both fast charging and the extension of the battery service life.
  • It has a rich variety of optional accessories, and users can choose to install SNMP cards, relays, dry contact cards, etc.

Green and Environmentally Friendly

  • It uses a standard 19-inch cabinet, which perfectly matches the application environment of the computer room.
  • When units are paralleled, they share the battery, greatly reducing the number of battery configurations.
  • The number of external batteries can be selected from 30 to 50, facilitating users to flexibly configure the batteries.
Model : HM33-FM 50-200 50-300 50-400 50-500 50-600
Capacity(KVA) Cabinet capacity 50-200 50-300 50-400 50-500 50-600
Power module 50
Maximum number of modules that can be installed 4 6 8 10 12
Input
Main input Rated input voltage 380/400/415Vac
Input Voltage 138-485Vac ; 305-485Vac linearly derating , 138-305Vac linearly derating
Input Wiring Three phase five wire
Input frequency range 40-70Hz
Input power factor ≥0.99
Input current harmonics (THDi) ≤ 3 % ( 100 % linear load)
Bypass input Rated input voltage 380/400/415Vac
Input Voltage 220Vac upper limit : 25 % ( optional+10%,+15%,+20% ) ; 230Vac upper limit : 20 % ( optional+10%+15% ) , 240Vac upper limit 15 % ( optional+10% ) ; Lower limit – 45 % ( optional-10%,-20%-30% )
Input Wiring Three phase five wire
Bypass synchronous tracking range ±10 %
Output
Voltage 380/400/415Vac±1 %
Power factor 1
Frequency (Hz) Mains power mode ±1%/±2%/±4%/±5%/±10 % can be set
Battery Mode (50/60±0.1%)Hz
Wave form sine wave
Peak current ratio 3:1
Output voltage harmonics (THDV) ≤ 2 % ( 100 % linear load ) ; ≤ 3 % ( 100 % non-linear load )
Transfer Time (ms) Switching from mains mode to bypass mode : 0ms ( tracking ) ; Switching from mains mode to battery mode : 0ms
Overall efficiency 96 %
Overload capacity 110 % load , continue for 60 minutes and then switch to bypass : 125 % load , continue for 10 minutes and then switch to bypass : 150 % load , continue for 1 minute and then switch to bypass
Battery
Maximum charging current of module (A) 20
Battery voltage Optional voltage 180V / 192V/204V/216//228V/240/±252/±264/±276/28 / ±300Vdc ( 30/32/34/36/38/40/42/44/46/48/50 sections , i.e. 30 to 50 cells are optional )
Environment
Operation temperature 0°C-40°C
Storage temperature -25 ° C-55 ° C ( excluding battery )
Humidity range 0-95 % ( non condensation )
Working altitude < 1500 meters ( use with derating according to GB/T 3859.2 for distances exceeding 1500 meters )
Noise (dB) (at a distance of 1 meter) < 65 68 < 70
Other functions
Caution function Multiple alarm functions such as overload , abnormal mains power , UPS failure , battery undervoltage , etc
Protection function Short circuit , overload , overheating , battery undervoltage , output undervoltage , fan fault alam , lightning protection , bypass backflow
Communication CAN , RS485 , Network interface , dry contact point , parallel interface , LBS interface , smart slot , temperature sensor interface
Physical properties
Size : D×W×H (mm) Cabinet 850×600×2000 850×600(1200)×2000 850×1200×2000
module 620×440×130
Net weight (Kg) Cabinet 203 235 257(407) 443 513
module 33
Execution standards YD/T 2165-2017